The Model eXGD3160F200 series covers superb high transient surge protection and AC power noise filtering at the main service panel for most applications which computing process sensitive high tech equipments. It will be guarded from damage, errors and downtime resulting from high speed transients and noise interruption.
The eXGD3160F200 series model achieve to protect extraordinarily high transient exposed AC power distribution line and Tracking noise filter circuit performs to clamp undesired pick noise exposed on AC sine wave. Models offer full mode protection and quick repair and replacement. The connection terminal for input and output consist of serial connection type.

Surge Protection Module.
Main & Branch & Local Service Panel Protection for 3 phase.
• Max surge protection capacity IP=160KA/Phase (8/20).
Front panel LED's for status indication and abnormal voltage detection(N-G).
High Performance surge Fuse : I.R=200KA Max (Dual Fusing).
All modes of protection, L-N, L-G, L-L, N-G.
Fast clamp response : less than one nano-seconds.
Bipolar/Bidirectional protection to prevent additional damage.
Powerful performance Surge Protection.

AC Power Tracking Noise Filter Module.
3 phase EMI / RFI AC power tracking filter.
Excellent Filtering for Normal Mode and Common Mode Noise.
Good reliability and high performance.
Outstanding noise absorption, particularly for high voltage impulse.
Low Leakage.
Suitable for Industrial, Medical Equipments, OAFA Equipments,

 

Enclosure for eXGD3160F200.
Enclosure : NEMA 1, AC(PC material) Water and sunbeam resistance.
Dimensions : 500mm(W) × 600mm(H) × 250mm(D)
Dual Door for alarm supervision and water proof

Surge Protector Module.
Operating Voltage rate : Maximum Allowable125% Rated Line Voltage 145%
                                     Rated Line Voltage(Option).
Response Time : < 1 Nanosecond.
Modes of Protection : L-N, L-G, L-L, N-G
Surge Current/Phase(8/20) : 160KA/1 Event.
Surge Life/Phase(8/20) : 6KA/10,000 Event.
Protection Present / reduced : Green : Normal Operation.
Operating Altitude : 13,000 ft. (4000m).
Abnormal Voltage Detection : Red LED Lamp : Between Neutral-Ground.
• Temp.(Operating) : -40 to + 70.
• Temp.(Storage) : -40 to + 85.
Enclosure : NEMA 1, 14gauge steel.
Dimensions : 160(W) × 198(H) × 68(D) [mm]
Power Cable : UL 1015 #10 AWG (High performance, Low inductance).
Noise Filter : EMI/RFI Filter included (UL1283).
Safety & performance : UL 1449 2nd Edition Spec. Meets.

AC Power Tracking Noise Filter Module.
• Maximum filter peak current : 200A.
• Rated voltage : Maximum 450V.
• Test voltage : 1,500Vrms between line and earth for 1 minute.
• Isolation Resistance : 500Vdc 300Mohm between line and earth.
• Leakage Current : 0.5 Max mA.
• Temperature Rise : 40 Max °C.
• Operating Temperature : -25 ~ +85 °C.

Surge Protector Suppression
Voltage Characteristic
 
Shown here is a typical clamp waveform of the Model eXGD3160F200
Using by 6KV(1,2/50
),3KA(8/20)
Test waveform.

AC Power Tracking Noise Filter attenuation Characteristic

Common Mode

Normal Mode (Differential Mode)

 

Model

Rated Voltage

Description

Suppression Voltage(8/20㎲)3KA

eXGD3160F200-120Y

120/208VAC

3P, 4W+Gnd, Wye

600V

eXGD3160F200-220Y

220/380VAC

3P, 4W+Gnd, Wye

980V

eXGD3160F200-240Y

240/415VAC

3P, 4W+Gnd, Wye

1200V

eXGD3160F200-240D

240VAC

3P, 3W+Gnd, Delta

1200V

eXGD3160F200-240DCT

240/120/120VAC

3P, 4W+Gnd, Hi-leg

600/1200V

*High-leg Delta Center Tapped